Start here to select a Dropair Mini6 or Mini6S interface for a supported air-conditioning installation. This guide summarizes the Mini6-series manual and links to brand-specific selection guides; the original wiring diagrams remain the installation reference.
Source: Mini6 / Mini6S Installation and Service Manual V7.3.2, 15 June 2026, pages 6–18.
Before choosing an adapter
Identify the indoor-unit model, original controller and PCB interface first. The manual distinguishes refrigerant systems using low-voltage controllers from chilled-water systems commonly controlled by 100–240 V thermostats; those chilled-water applications require a Pro-series review. Mini6X is a separate gateway with its own manual and is not covered by this Mini6 / Mini6S installation guide.
- Check the complete indoor-unit model and control interface, then verify the adapter label, firmware and supplied cable against the chosen solution.
- Test the air conditioner with its original controller before making changes. Record any existing faults.
- A qualified installer must isolate and verify the electrical supply before wiring. Mini6 / Mini6S have a 100–240 VAC input; their thermostat output is 24 VAC. These are not interchangeable connections.
- Follow the exact brand diagram and retain the original controller unless that diagram specifically requires removal. Do not translate one brand’s terminal assignments to another.
- Connect the supported thermostat using the model-specific thermostat diagram and correctly terminated T568B CAT5/CAT6 cable. The RJ45 socket is not Ethernet and must never connect to a router or switch.
- After wiring checks, commission the configured heating/cooling and fan functions supported by the actual equipment. Thermostat models have different terminal definitions and fan-speed capabilities.
Brand-specific Mini6 guides
Other AC brands documented in the manual
The following sections provide an initial selection reference. Each route remains conditional on the exact hardware, firmware and cable. Open the linked manual pages to inspect the original diagrams.
Carrier
CR-AB: two-wire A/B controller, Mini6S. CR-CN10: CN10/CN10A PCB route, Mini6; supplied CR-CN10-10P cable. If yellow CN10 and white CN15 both exist, the manual directs connection to CN15. A yellow-only CN10 requires the separately documented cable arrangement.
Source: Mini6 / Mini6S Installation and Service Manual V7.3.2, 15 June 2026, pages 31–32.
Toshiba
TS-AB: two-wire A/B controller, Mini6S. TS-CN2: Mini6 through the 11-pin CN2 on the back of RBC-ASC11E or RBC-ASCU11 remote controllers. These are controller model identifiers, not indoor-unit model numbers.
Source: Mini6 / Mini6S Installation and Service Manual V7.3.2, 15 June 2026, pages 34–35.
Midea and listed related brands
MD-CN10: Mini6 for the documented CN10/CN10A interface. The section names Super General, System Air, Lennox, Cooper Hunter, Vaillant, Bosch, ECOX, SURREY and SKM. When both yellow CN10 and white CN15 exist, use the documented CN15 route; a yellow-only CN10 may require CR-CN10-Yellow. Do not assume all products sold under these brands share the same PCB.
Source: Mini6 / Mini6S Installation and Service Manual V7.3.2, 15 June 2026, pages 38–39.
Lennox
LN-CN10: Mini6 with the matching CN10 cable and controller-removal arrangement. Listed examples: 4MCDUA18TB, 4MCDUA24TB, 4MCDUA30TB, 4MCDUA36TB, 4MCDUA36TD, 4MCDUA48TD and 4MCDUA60TD. LN-H1H2: Mini6S with a two-wire H1/H2 controller.
Source: Mini6 / Mini6S Installation and Service Manual V7.3.2, 15 June 2026, pages 39–40.
Trane
TR-CN10 and TR-CN29 are documented PCB routes; TR-H1H2 is the two-wire controller route. Page 41 lists the same 4MCDUA examples as the Lennox section; confirm the actual brand label and PCB before selection. The manual directs Trane fan-coil units to the Pro series rather than assuming a Mini6 installation.
Source: Mini6 / Mini6S Installation and Service Manual V7.3.2, 15 June 2026, pages 41–42.
Hitachi
HT-AB: Mini6S with a suitable two-wire controller. Some older units cannot share two wired controllers; the manual discusses an IR alternative with a PC-P1H8Q receiver-equipped controller. HT-X940: Mini6 route for the described four-wire-controller PCB arrangement.
Source: Mini6 / Mini6S Installation and Service Manual V7.3.2, 15 June 2026, pages 43–44.
Mitsubishi Heavy Industries
MH-XY: Mini6S for the documented two-wire controller arrangement. MH-CN29 is also illustrated, but the compatibility table does not separately assign a hardware model for it. Obtain confirmation rather than borrowing Mitsubishi Electric settings.
Source: Mini6 / Mini6S Installation and Service Manual V7.3.2, 15 June 2026, pages 44–45.
Panasonic
PS-AB: Mini6S with a two-wire A/B controller. PS-CN10: Mini6 with a CN10/CN10A socket and the prescribed controller removal. PS-CNDISP: CN-DISP arrangement; the manual names CS-D43DD2H5 as a typical indoor-unit example.
Source: Mini6 / Mini6S Installation and Service Manual V7.3.2, 15 June 2026, pages 45–46.
Gree
GR-H1H2: Mini6S for the documented two-wire H1/H2 controller. The standard original-controller automatic-off communication test is specifically excluded for Gree on page 18; follow its required thermostat test.
Source: Mini6 / Mini6S Installation and Service Manual V7.3.2, 15 June 2026, pages 46–47.
Hisense
HS-AB: Mini6S for the two-wire A/B controller route. HS-X940: Mini6 for the CN7/X940 PCB route on the described four-wire-controller system; the section names cable YK-CN7-10P.
Source: Mini6 / Mini6S Installation and Service Manual V7.3.2, 15 June 2026, pages 47–48.
Chigo
CN-CN23: Mini6 for the CN23 ten-pin socket arrangement. The manual names the YK-CN6 cable arrangement; use a supplied, correctly labelled cable rather than treating CN23 as compatible with an arbitrary ten-pin lead.
Source: Mini6 / Mini6S Installation and Service Manual V7.3.2, 15 June 2026, pages 48–49.
Haier
The manual labels its two-wire-controller route MH-AB and shows P1/P2; the compatibility table assigns Haier two-wire installations to Mini6S. HR-CN29 is also illustrated, but its hardware assignment should be confirmed separately before ordering.
Source: Mini6 / Mini6S Installation and Service Manual V7.3.2, 15 June 2026, pages 50.
Wired or infrared control?
Use the documented wired connection where available. For the IR option, confirm the receiver and matching firmware, position the transmitter as shown, and keep the optical path clear. The manual describes an optional extended IR sender. Its extended-sender arrangement is restricted to single-air-conditioner control and must not be assumed suitable for combined AC/floor-heating or AC/ventilation configurations.
Source: Mini6 / Mini6S Installation and Service Manual V7.3.2, 15 June 2026, pages 50–51.
Thermostat selection and commissioning
Use the exact thermostat diagram: Nest Learning Thermostat on pages 53–58, ecobee on pages 59–62, standard 24 VAC arrangements on pages 63–64, Lutron Palladiom on page 65, and the separately interfaced 220 VAC thermostat arrangement on page 66. Do not wire a 220 VAC thermostat to the 24 VAC RJ45 port. The manual specifies an iPanel intermediary for the listed 220 VAC thermostat route.
Check cooling, supported heating, fan operation and shutdown after commissioning. Do not assume displayed setpoints must match between Nest and the original controller. Diagnose faults using pages 67–70, and keep a record of the selected interface, adapter label and cable for future service.
What the manual does—and does not—confirm
The manual provides interface conditions and selected model examples; it is not an exhaustive list of every regional AC model. Where a compatibility-table entry and a detailed section use different identifiers, request confirmation rather than guessing. Additional brand names in the shared CN10 section are conditional PCB examples, not blanket support for the manufacturer’s full range.
Confirm your installation
Send the complete indoor-unit model, controller model, clear terminal/PCB photos, thermostat model and required functions. Dropair can check the matching hardware, firmware and cable before you order.
Request a compatibility check · Mini6 details · Mini6S details · Manual library